The Telemecanique (Schneider Electric) LC1D09 3-pole contactor and the TeSys LRD12 thermal overload relay combine to form a direct-online motor starter. The LRD12 plugs directly into the bottom terminals of the LC1D09, providing adjustable overload protection for 3-phase motors drawing between 5.5A and 8.0A
9A inductive rating (AC-3), 25A resistive rating (AC-1), handles up to 4 kW at 400V (5 HP at 480V)
Adjustable current range of 5.5A to 8.0A, Class 10A trip rating, includes built-in 1 N.O. and 1 N.C. auxiliary signaling contacts